Davayla ilgili ayrıntılar
Evde / Davalar /

Şirket vakaları hakkında How to Select 4‑20 mA Signal Cables

How to Select 4‑20 mA Signal Cables

2026-09-03

In automation‑control engineering projects, the selection of 4‑20 mA signal cables directly determines system anti‑interference performance, signal transmission accuracy and long‑term operational reliability. Combining industry standards and field engineering practices, precise cable selection can be performed from the following five core dimensions.

I. Core Construction and Anti‑Interference Design

The 4‑20 mA signal is a weak analog signal highly susceptible to electromagnetic interference from on‑site sources such as frequency converters, large electric motors and welding machines. Therefore, cable construction must satisfy the following requirements.

son şirket davası hakkında How to Select 4‑20 mA Signal Cables  0

1. Twisted‑Pair Structure

Twisted‑pair cables are mandatory. The symmetry of twisted pairs offsets interference induced by external electromagnetic fields. Shorter twist pitches deliver stronger anti‑interference capability.

2. Group‑Based Shielding

Adopt a layered‑shield S/FTP structure: individual aluminium‑foil shielding for each pair plus overall copper‑braid shielding. This effectively mitigates crosstalk between pairs and external common‑mode interference.

3. Pure‑Copper Conductors

High‑purity copper conductors (copper content ≥ 99.9 %) shall be used. Aluminium‑core or copper‑clad‑aluminium conductors are strictly prohibited, to guarantee sound conductivity and prevent oxidation and overheating at joints.

4. Insulation‑Layer Materials

Insulation shall be polyethylene (PE) or polyvinyl chloride (PVC), with insulation resistance ≥ 500 MΩ·km. PE insulation offers a lower dielectric constant and superior high‑frequency performance, suited for high‑speed data‑transmission scenarios.

II. Conductor Cross‑Section vs. Transmission Distance

Loop voltage drop shall be calculated during selection to guarantee that the voltage at the transmitter terminal remains above its minimum operating voltage (typically ≥ 16 V) at maximum transmission distance. Below are reference selections for standard 24 V power‑supply systems.

Transmission Distance Recommended Cross‑Section Approximate Loop Resistance Remarks
Within 100 m 1.0 mm² ≤ 3.6 Ω Cost‑effective for basic requirements
100 m ~ 300 m 1.5 mm² ≤ 2.4 Ω Most‑common standard size for automation projects
300 m ~ 800 m 2.0 mm² or 2.5 mm² ≤ 1.8 Ω / ≤ 1.2 Ω Restrain voltage drop caused by line resistance
Above 800 m 2.5 mm² ≤ 1.2 Ω Strict voltage‑drop verification required; for distances exceeding typical limits (1000‑1500 m), install signal isolators or repeaters

Voltage‑drop calculation formula:

ΔU = I × R × L × 2

Where: ΔU = loop voltage drop (V); I = loop current (mA); R = resistance per unit length (Ω/km); L = one‑way transmission distance (km).

III. Jacket Material and Environmental Compatibility

Cable outer jackets shall be selected according to actual installation environments.

Application Scenario Recommended Jacket Material Properties Applicable Standards
General indoor / cable‑tray routing PVC Cost‑effective, flame‑retardant, resistant to mild chemical corrosion GB/T 19666
Inside control cabinets / densely‑occupied areas LSZH (Low‑Smoke Zero‑Halogen) Releases no toxic gas during fire; light transmittance ≥ 60 % GB/T 19666, IEC 61034
Harsh industrial environments (oil contamination, chemicals) PUR (Polyurethane) or CPE Oil‑resistant, abrasion‑resistant, acid‑alkali‑resistant, low‑temperature‑resistant HG/T 2006
Frequent movement / drag‑chain applications High‑flexibility PUR Bending cycles ≥ 1 million, torsion‑resistant VDE 0295

IV. Key Installation and Grounding Specifications

Proper cable selection is only the first step; correct installation also determines final performance.

1. Single‑Point Shield Grounding

The cable shield must be reliably grounded only at the control‑cabinet (PLC/DCS card‑module) end. The shield at the field‑instrument end shall be insulated and floating. Grounding both ends is forbidden, as ground‑potential differences create ground loops that introduce severe interference and signal drift.

2. Segregation of Low‑Signal and Power Cables

4‑20 mA signal cables shall never share conduits or cable trays with power cables (e.g., 380 V supply cables, frequency‑converter output cables). For parallel routing, maintain a minimum clear separation of 30 cm. Where crossing is unavoidable, route cables at a 90‑degree perpendicular angle.

3. Minimum Bending‑Radius Control

Avoid sharp bends or kinks during installation. The minimum cable bending radius shall be no less than 6‑7.5 × the outer cable diameter, to prevent internal‑insulation damage or broken shield braid wires.

4. Conduit Protection

Route cables inside galvanised‑metal conduits or cable trays; both ends of metal conduits shall be reliably grounded. Conduit fill factor shall not exceed 40 % to ensure heat dissipation and maintenance space.

V. Common Selection Pitfalls and Mitigations

Common Pitfall Potential Risk Correct Practice
Copper‑clad‑aluminium conductors Joint oxidation, higher contact resistance, signal attenuation Specify high‑purity oxygen‑free copper conductors
Shield grounded at both ends Ground‑loop interference, signal drift Ground shield only at the control‑cabinet end
Shared trays with power cables Electromagnetic‑coupling interference, signal distortion Separate trays; maintain ≥ 30 cm clearance
Neglecting voltage‑drop calculation Insufficient power supply for remote instruments, abnormal signals Calculate voltage drop per formula; add repeaters if necessary
Jacket mismatched to operating environment Jacket cracking and ageing, insulation failure Select jacket material matched to site conditions

VI. Quick‑Reference Selection Table

Application Scenario Conductor Material Shielding Structure Jacket Material Conductor Size
Standard DCS / PLC control cabinet Oxygen‑free copper Aluminium‑foil + copper‑braid double shield PVC 1.5 mm²
Near frequency converters / high‑interference zones Oxygen‑free copper S/FTP double‑layer shield PVC 1.5‑2.5 mm²
Petrochemical / hazardous‑explosion areas Oxygen‑free copper Aluminium‑foil + copper‑braid double shield LSZH 1.5‑2.5 mm²
Outdoor / harsh environments Oxygen‑free copper Aluminium‑foil + copper‑braid double shield PUR/CPE 2.5 mm²
Long‑distance transmission (> 800 m) Oxygen‑free copper S/FTP double‑layer shield PVC / LSZH 2.5 mm² plus repeater

Closing Remarks

Selecting 4‑20 mA signal cables is a systematic engineering task. Signal integrity, electromagnetic compatibility, environmental durability and installation specifications must all be considered comprehensively. Engineers shall fully investigate site operating conditions before selection, strictly follow relevant national standards, and enforce quality control over critical steps such as shield grounding during installation, to guarantee stable long‑term operation of automation‑control systems.

Reference Standards

‑ GB/T 19666‑2019 General Rules for Flame‑Retardant and Fire‑Resistant Electric Cables and Optical Cables

‑ GB/T 5023‑2008 Polyvinyl‑Chloride‑Insulated Cables of Rated Voltages up to and Including 450/750 V

‑ HG/T 2006‑2022 Thermoplastic Polyurethane Elastomers

‑ IEC 61034‑2 Measurement of Smoke Density of Cables Burning under Specified Conditions

‑ GB 50057‑2010 Code for Design of Building Lightning Protection

‑ SH/T 3019‑2016 Specification for Design of Instrument Piping and Cabling in Petrochemical Engineering